SX-HEC25

SIGNUX HEC25

What soil needs measuring, and nothing more

Soil probe for moisture, conductivity and temperature, with RS485 Modbus RTU output. A 2 m cable, with a stripped end or an M10 connector.

The three prongs go into the soil and measure moisture, conductivity and temperature at the same point. That is the combination a watering decision needs: how much water there is, how much salt has built up, and what temperature the soil is at.

The body is vacuum-potted in flame-retardant epoxy resin, rated IP68, and stands being buried long term without electrolysis eating the contacts. It speaks Modbus RTU over RS485, with no gateway in between.

Measures
Moisture · Conductivity · Temperature
Output
Protection
IP68
Operating
−20 to +80 °C
HEC25 probe on a white background: a black rectangular body with an orange label and three steel prongs

What sets it apart

One hole, one reading

All three come from the same point and in the same Modbus frame: three consecutive registers from 0x0000. Nothing to line up between probes driven in at different depths.

Calibrated by drying and weighing

Checked against the gravimetric reference method: the sample weighed wet, then dry. And the salt content of the soil barely affects it, so it works in any kind of ground.

Made to stay put

Vacuum-potted in black flame-retardant epoxy, with IP68 that allows immersion and resistance to long-term electrolysis.

The prongs go all the way in

70 mm long and 3 mm across, and the reading needs them fully buried: if one is left in the air, the figure is worthless.

Configurations

Cable lengthConnector / outputPart number
2 mPigtailSX-HEC25-2M-PT
2 mM10 connectorSX-HEC25-2M-M10

Specifications

General

Measured parameters
Moisture · Conductivity · Temperature
Family
Direct-insertion probe
Output
RS485Modbus RTU
Prongs
3 pcs

Soil moisture

Range
0-100 %
Resolution
0.1 %
Accuracy
±2 %Over the 0-50 % span
±3 %Over the 0-100 % span

Electrical conductivity

Range
0-20000 µS/cm
Resolution
10 µS/cm
Accuracy
±3 %Up to 10,000 µS/cm
±5 %At 20,000 µS/cm

Temperature

Range
−40 to +80 °C
Resolution
0.1 °C
Accuracy
±0.5 °C

Output and power

Output interface
RS485Modbus RTU protocol
Power supply
5 to 30 V DC
Maximum consumption
0.7 WAt a 24 V DC supply
Factory settings
4800 8N1, address 1
Baud rates supported
2400 · 4800 · 9600

Construction

Ingress protection
IP68
Operating temperature
−20 to +80 °CAt 0 to 80 % RH
Sealing
Flame-retardant epoxy resin, vacuum-potted
Prongs
70 × ⌀3 mmLength by diameter
Cable length
2 m

Manual

1Introduction

The HEC25 measures soil moisture, conductivity and temperature at the same point, and delivers them over RS485 in Modbus RTU.

It measures from −40 to +80 °C with an accuracy of ±0.5 °C, from 0 to 100 % moisture with ±2 % over the lower half of the scale, and from 0 to 20,000 µS/cm of conductivity with ±3 % up to 10,000.

The three prongs are vacuum-potted in flame-retardant epoxy resin, rated IP68. It is meant to stay buried, not for a single campaign.

2How to order it

The unit is always the same; what is chosen when ordering is the cable length and how it ends.

TerminationWhat for
M10 connectorIt plugs and unplugs without tools and without touching the terminal block
Bare wiresA stripped end, to go straight into a terminal block

The cable is two metres as standard. Other lengths on request.

3Where to install it

The prongs have to go fully into the soil: if one is left in the air, the reading is worthless. Four things that change the figure more than any setting:

  • •A spot with no stones, so that no prong meets anything hard.
  • •Clear the top layer down to the depth the reading matters at, and push the probe vertically into the undisturbed soil below.
  • •Push it in once, without rocking it side to side: a gap around the prongs falsifies the reading.
  • •On a small spot, take several readings and use the average.

If the ground is hard, first drill a hole smaller in diameter than the prongs, insert the probe and compact the soil around it before measuring.

To leave it in place: dig a vertical pit more than 20 cm across, push the probe into the pit wall at the depth that matters, fill it back in firmly and let it settle. From then on it can measure and log for days or months.

Conductivity needs water to be reliable: the electrode measures the dissolved soluble ions, and below about 20 % volumetric water content the figure falls short. Over long-term monitoring, the value after watering or rain is the one closest to the true level; if a quick reading is needed, water the spot and wait for it to soak in.

4Warnings

  • •The prongs have to end up completely inside the soil.
  • •Do not leave it in direct sun: the body is black and can go past 50 °C. The temperature read would not be the soil’s.
  • •Do not bend the prongs, do not pull it out by the cable and do not knock it about.
  • •The IP68 rating allows it to be submerged.
  • •Do not leave it powered up in open air for long.

5Connection

The unit comes out with four wires. Two are the supply and two are the bus:

WireWhat it is
BrownPositive supply, 5 to 30 V DC
BlackNegative supply
Yellow485-A
Blue485-B

Mind the colour: here A is the yellow wire. If the unit answers nothing at all, the first thing to try is swapping the yellow and the blue.

With several units on the same bus, or a long cable run, bring the supply close to the unit, add an RS485 repeater and fit a 120 Ω terminating resistor at both ends.

6Reading the unit over RS485

Modbus RTU, from the factory at 4800 8N1 and at address 1. It takes 2400, 4800 and 9600.

For reading there is function 03. Function 04 returns the same thing, so either will do.

For writing there is 06, which writes one register. Eight registers accept it: the three coefficients, the three calibrations, the address and the baud rate. The five readings are read only.

6.1What can be read

RegisterPLCWhat it isScaleAccess
0x000040001Moisture÷ 10Read only
0x000140002Temperature, signed÷ 10Read only
0x000240003Conductivity—Read only
0x000340004Salinity, calculated—Read only
0x000440005TDS, calculated—Read only
0x002240035Conductance temperature coefficient÷ 10Read and write
0x002340036Salinity coefficient÷ 100Read and write
0x002440037TDS coefficient÷ 100Read and write
0x005040081Temperature calibration, signed÷ 10Read and write
0x005140082Moisture calibration, signed÷ 10Read and write
0x005240083Conductivity calibration, signed—Read and write
0x07D042001Bus address, 1 to 254—Read and write
0x07D142002Baud rate: 0 = 2400, 1 = 4800, 2 = 9600—Read and write

Temperature and the three calibrations come signed, in two’s complement: a value above 32767 is negative. FF 9B is −101, that is −10.1 °C.

6.2Frame examples

All the frames are for a unit at address 1 and already carry their CRC.

1 · Read the moisture, the temperature and the conductivity

FrameDirection
01 03 00 00 00 03 05 CBsent
01 03 06 02 92 FF 9B 03 E8 D8 0Freply

Three registers (00 03) from 0x0000. The reply brings six bytes (06): 02 92 is 658, that is 65.8 % moisture; FF 9B is −101, that is −10.1 °C; and 03 E8 is 1000 µS/cm. Negatives come in two’s complement.

2 · Read all five readings in one go

FrameDirection
01 03 00 00 00 05 85 C9sent

The five readings sit together from 0x0000, so they are asked for at once: five registers (00 05). The reply brings ten data bytes (0A) in this order: moisture, temperature, conductivity, salinity and TDS. Measured on the bench at 4800, the unit takes 63 ms in the worst case to answer this request.

3 · Read the three coefficients

FrameDirection
01 03 00 22 00 03 A5 C1sent

The three sit together from 0x0022. From the factory they read 0, 55 and 50: temperature coefficient 0.0 %, salinity coefficient 0.55 and TDS coefficient 0.50. Measured that way on the bench unit.

4 · Change the address to 2

FrameDirection
01 06 07 D0 00 02 08 86sent

The address number goes in 0x07D0, from 1 to 254. We have not tried this one on the bench: the frame is put together from the register map.

5 · Set the baud rate to 9600

FrameDirection
01 06 07 D1 00 02 59 46sent

The baud-rate code goes in 0x07D1: 0 is 2400, 1 is 4800 and 2 is 9600. This one has not been tried on the bench either.

Documentation

Does it fit your case?

Tell us where the SX-HEC25 is going and what you need to integrate it with. We’ll tell you whether it’s the right device — and if not, which one is.

See the catalogue